Serial Communication
Two serial communication ports are provided by the IQ-400
controller.
RS-485: Four wire (twisted pair) interface which is optically
isolated from the controller.
Provision for installing a termination resistor is provided.
RS-232: At P7 (RS232 DB9 – Real Time Printer Port). At
P2 (RS232 Direct Connect) – standard RS232 interface.
Jumper W6 adds/removes an onboard 120Ω End-of-Line
Termination Resistor.
Power Supply
The IQ-400 controller requires +5VDC for all logic. Relays,
output drivers, etc. require a +12VDC supply. An on-board dc-
dc converter accepts an external voltage source of 10-26VDC,
and converts this unregulated source to the required +5VDC.
For an input voltage range of 10-15 volts, the “+12VDC”
converts this voltage source to the required +12VDC. For more
information, please refer to the ESD power supply installation
manual.
Battery Back-up Requirements
A 12 AH battery is recommended as a back-up to the power
supply, because it is the largest battery that will fit in the
enclosure. The battery should be connected to the power
supply charger in accordance with the manufacturers
instructions. Refer to ESD SPS-3.6M2E, or SPS-6.5M4 Power
Supply installation instructions (P/N: SPS36instructions Rev:
04/15/02) for determining battery backup size.
Factory Settings
At the factory the IQ-400 is set as IQ-400 #1, communications
as direct connect (RS232/RS485) @ 9600 baud, with 120 Ohm
resistor termination disabled (W6 jumper set at 1-2).