Sharp IQ-8000 Manual de instalación Pagina 75

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 125
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 74
7.8 Communicating with Multiple IQ-400s (via RS-485)
Once the PC host is connected to one IQ-400, the next IQ-400 can be connected by wiring from
P3 from the first IQ-400 to P4 in the next IQ-400. This format can be repeated in up to 16
IQ-400s. In addition, any combination of MicroLPMs and IQ-400s can be configured up to the 16
total limit on a single RS485 channel. LiNC-NET supports up to 4 channels (total of 64 IQ-400/
MicroLPMs). See the next page for the IQ-400 to MicroLPM wiring connection.
NOTE: For UL 1076 installations, refer to the Linc-Net Admin Guide.
7.8.1 Wiring Diagram of Multiple IQ-400s and Other Panels
Page lxii of 110 IQ-400 Installation Manual 33-10057-001-C
Vista de pagina 74
1 2 ... 70 71 72 73 74 75 76 77 78 79 80 ... 124 125

Comentarios a estos manuales

Sin comentarios