9.4 IQ 8-Reader Expansion Module (P/N: 03-10102-201E)
The IQ-400 4-reader system can be expanded to a 12-reader system by installing the 8-Reader
Expansion Module. The 8-Reader Expansion board can be mounted below the IQ-400 in the larger
enclosures available from PCSC. Once mounted, the 8-Reader Expansion board is connected to the
IQ-400 by installing a 50-pin ribbon expansion cable from P1 on the 8-reader Expansion board to J1 on
the IQ-400. The 8-Reader expansion board allows the user to connect up to 8 additional readers to the
IQ-400. Each of the reader interfaces support either a PCSC proprietary reader (4-wire interface), or a
Wiegand reader (5-wire interface). The Expansion board also provides 8 additional interfaces for each of
the readers and the associated doors. These include the following:
•
Multilevel Door Sense Inputs (Supervised door sense inputs)
•
Reader Present inputs (Reader connected/disconnected)
•
Request to Exit inputs (Supervised Egress Inputs)
•
Relay contacts for door control outputs (Form C dry contacts rated for 2.0 Amps @ 12/24VDC
continuous power)
•
Door shunt/Local Alarm/Outputs (Open Collector output rated for +12 VDC @ 100mA)
9.4.1 Electrical Ratings
Power: 12VDC
Draw: 160mA @ 12V
Relay Contacts 2 A @ 24 VDC
Data0/Data1 5 Vdc @ 0 mA for Logic 1
0 Vdc @ 5mA for Logic 0
Card Reader Draw: 100mA @ 12 VDC
Alarm Point Voltage 5.0 Vdc @ 0.0 mA when Sense Input is in Open Circuit Physical State.
& Tamper Voltage 0.0 Vdc @ 5.0 mA when Sense Input is in Short Circuit Physical State.
1.6 Vdc @ 3.4 mA when Sense Input is in Alarm Physical State.
0.9 Vdc @ 4.1 mA when Sense Input is in Normal Physical State.
9.4.2 Power Supply
The 8-reader Expansion Module requires +5VDC for all logic. Relays, output drivers, etc. require a
+12VDC supply. The +5VDC and +12VDC is provided to the module via the 50-pin expansion cable,
which connects plug P1 of the 8-door cluster PCB (P/N 03-10102-201E) to plug J1 of the IQ-400 board,
(P/N 03-10111-201). The Variable Ambient Test will be for Indoor, 0 to 49 Degrees C, and 85% Relative
Humidity @ 30 Degrees C.
Page xciii of 110 IQ-400 Installation Manual 33-10057-001-C