8.4 Proper Setting of SAM 1 and SAM 2
In a system that uses SAM 1 as a stand-alone, the W1 switch must be set to LOW
(Pins 2-3).
In a system that uses both SAM 1 and SAM 2 together, SAM 1 needs to be set to LOW
(Pins 2-3) and SAM 2 needs to be set to HIGH (Pins 1-2).
Page lxxiii of 110 IQ-400 Installation Manual 33-10057-001-C