7.4.1 Ensuring Proper Configuration of the MODEM
To ensure that the MODEM retains the set configuration, the user should utilize HyperTerminal at
the Host PC. The HyperTerminal program will set the configuration in the MODEM for constant
uninterrupted use with the IQ-400. In the following procedure, the Init String will be written into the
NOVRAM and therefore a power loss to the MODEM ONLY will not result in a continuous loop.
•
Set switches 1, 5, 6, and 7 in the U.S Robotics Sportster MODEM (14.4K, 28.8, 33.6, or
56K) to Up. All other switches should be Down.
•
Connect the MODEM to the PC using a standard PC to MODEM cable.
•
From the PC (Win95/98/NT) access HyperTerminal by entering the following commands:
1. Click on Start: Programs: Accessories, and then, HyperTerminal. The
Connection Description dialog box will now appear.
2. Type in a name for the connection (for example: MODEM TEST). Click on a
corresponding icon from the list. Click on the OK button.
3. The Connect To dialog box will now appear. The proper communications port used
to communicate to the external MODEM is now selected within the Connect Using
field (for example: COM2). Click on the OK button.
4. The COM# Properties dialog box will now appear. Select 9600 in the bits per
second field. Select 8 in the Data Bits field, None in the Parity field, 1 in the Stop
Bits field, and Hardware in the Flow control field. Click on the OK button. The
screen will now clear and the cursor will be at the top left corner of the
HyperTerminal window. Type ATV1 E1 and press Enter. The MODEM will respond
with OK.
5. Type ATI3 and press Enter to display the type of MODEM connected, followed by
OK.
6. Type ATI4 and press Enter to display the MODEM’s current settings, followed by
OK.
7. Type ATI5 and press Enter to display the MODEM’s NVRAM settings, including any
stored telephone numbers, followed by OK.
8. Type ATEVQHSØ=1X&DØ and press Enter. The MODEM will respond by
changing the A in the previous String to a Ø (zero).
9. Type AT&WØYØ and press Enter. No visual indication will be displayed as the
MODEM was configured in the previous step to use Numeric Result Codes.
10. Type ATZ and press Enter. As in the previous step, no visual indication will be
displayed.
11. Click on File, then Save, to save the configuration file.
12. Click on File, Exit, then Yes, to disconnect from the MODEM and exit
HyperTerminal.
13. Power down the MODEM and turn switch 1, 5, and 6 up. All others should be
down. Connect the MODEM to the IQ-400. Perform functional testing.
Page liv of 110 IQ-400 Installation Manual 33-10057-001-C