2 - 95
SIEMENS PC • 4
(S7-200 PPI)
2 SIEMENS PC • 4
3 3
Available PLC
S7-200 series
RS-422 [Wiring Diagram 1]
S7-200 PPI
PC
Wiring Diagram
(refer to P2-96)
ZM-71SE
Model Setting
Communication Setting
The recommended communication parameter setting of both PLC and ZM-** is as follows:
9600bps
2
Even (fixed)
Baud Rate
Port
Parity
Item Setting of PC
9600bps
2
Comm. Parameter of ZM-**
Available Memory
Memory Bit Write TYPE Remarks
V (data memory) 0 VW as word device
I (input) 1 IW as word device
Possible to write only to the area which is not used
Q (output) 2
M (bit memory) 3
T (timer/current value) 4
C (counter/current value) 5
TB (timer/contact) 6 Read only
CD (counter/contact) 7 Read only
HC (high speed counter/contact) 8 Possible to use double words
AIW (analog input) 9
AQW(analog output) 10
SM
(special memory/special relay)
11 SMW as word device
S (stage) 12 SW as word device
Set the memory to the extent of the memory range of each PC model. In case of using the [Bit Write] memory as the
bit device of the [Output Action] is [Momentary W], the other bits will be cleared when the bit memory is output,
because the [Bit Write] will be output by one word (refer to P5-10, reference 14-7 of ZM-71SE Instruction Manual).
Use [TYPE] number to assign indirect memory for macro programs.
Available: Unavailable: