2 - 89
Available Memory
SIEMENS PC 1
(S5-90, S5-95U, S5-100U)
Available PC
3 0
Communication Setting
Memory Bit Write TYPE Remarks
DB (data register) 0 Use memories more than DB3.
I (input relay) 1 IW as word device Read only
Q (output relay) 2 QW as word device Read only
F (internal relay) 3 FW as word device Read only
T (timer/current value) 4 Read only
C (counter/current value) 5 Read only
AS (absolute address) 6 Can not be used in S7 series.
<E.g.> DB003000
Block No.
Address No.
PC Link Unit
Wiring Diagram
(refer to P2-90)
S5-90U
S5-95U
S5-100U
S5-95U
RS-232C [Wiring Diagram 1]
RS-232C [Wiring Diagram 2]
CP-512SI
(3964R Transmission Protocol)
Second serial interface
(3964R Transmission Protocol)
ZM-71SE
Model Setting
S5/S7
* 1
9600bps
Even parity
8
Baud Rate
Parity
Transmission
Code
Data Length
Stop Bit 1
Item Setting of PC
9600bps
NOBusy Signal
OFF (fixed)Hand Shake
Even
8
1
Comm. Parameter of ZM-
**
The recommended communication parameter setting of both PC and ZM-
**
is as follows:
A similar program as RK512 is required.
*1 With the S5-95U second interface, the SIEMENSs converter 6ES5 734-1BD20 must be used.
Another cable connecting ZM-
**
and the SIEMENSs converter is required, because this
converter to ZM-
**
cannot be directly connected.
The assigned memory is indicated while editing
the screen as illustrated:
2 SIEMENS PC • 1
Available: Unavailable:
Declare more than 1 word of DB3 (data register) in PLC side previously. If not so, ZM-** cannot commu-
nicate with this PLC. Also, it is necessary to declare DB to be used in the software previously.
Vista de pagina 164