2 - 41
Matsushita PC
Available PC
Port 0 for both STATION x10 and x1
19200bps
Even
7 (ASCII)
Computer link system
Invalid
Baud Rate
Parity
Transmission
Code
Data Bit
Stop Bit 1
Transmission Control
Control Signal
Item Setting of PC
0
19200bps
Even
7
1
Comm. Parameter of ZM-
**
Communication Setting
FP1
FP0
FP3
FP5
FP10
RS-232C port
on a CPU unit
RS-232C port
on a CPU unit
AFP3462
AFP3463
AFP5462
AFP5462
RS-232C tool port
on a CPU unit
RS-232C cable made by Matsushita
AFC8513
PC Link Unit
Wiring Diagram
(refer to P2-43)
RS-232C [Wiring Diagram 1]
RS-232C [Wiring Diagram 1]
RS-422 [Wiring Diagram 4]
RS-232C [Wiring Diagram 1]
RS-422 [Wiring Diagram 4]
RS-232C [Wiring Diagram 1]
RS-232C [Wiring Diagram 1]
RS-232C [Wiring Diagram 1]
RS-232C [Wiring Diagram 3]
FP10S
RS-232C port
on a CPU unit
RS-232C port
on a CPU unit
AFP3462
AFP3463
RS-232C [Wiring Diagram 1]
ZM-71SE
Mode Setting
MEWNET
FP2
RS-232C tool port
on a CPU unit
RS-232C cable made by Matsushita
AFC8513
RS-232C [Wiring Diagram 2]
RS-232C port
on a CPU unit
* If a tool port (the ladder port for RS-232C) of FP0 is used, the range of PC parameter setting is
limited as below. Adjust PC parameter setting to comm. parameter setting of ZM-
**
.
Baud rate : 9600, 19200bps
Parity : Odd (fixed)
Data bit : 8 (7 can be selected. Normally 8.)
Stop bit : 1 (fixed)
The recommended communication parameter setting of both PC and ZM-
**
is as follows: