2 - 57
FUJI PC • 1
(MICREX-F series)
Available PC
1 9
Communication Setting
Port
Transmission
Control Mode
RS-232C
RS-422
1 (Asynchronous non-protocol by command)(fixed)
3 (Asynchronous non-protocol by command)(fixed)
0
19200bps
Even
7 (ASCII)
Provided
Baud Rate
Parity
Transmission
Code
Data Length
Stop Bit 1
Termination resistance at Receiver
Item Setting of PC
0
19200bps
Even
7
1
Comm. Parameter of ZM-
**
PC Link Unit
Wiring Diagram
(refer to P2-59)
F70, F70S
NC1L-RS2
NC1L-RS4
FFU120B
FFK120A
RS-232C [Wiring Diagram 1]
RS-485 [Wiring Diagram 2]
RS-232C [Wiring Diagram 1]
RS-485 [Wiring Diagram 2]
F80H, F120H, F120S
F140S, F15□S
ZM-71SE
Model Setting
MICREX-F
Series
(MICREX-F series
ZM70)
F55 NV1L-RS2
RS-232C [Wiring Diagram 1]
Switch Setting
MODE Switch: RS-232C: 1 RS-485: 3
RS-485 Port Setting SW: "0" for both x10, x1
RS-485 Termination resistance: ON
Character Switches
8
No
7
6
ON
ON
ON
Setting Contents
Switch setting
Parity provided
Even
5
ON 7 bit
4
ON 1 bit
2
ON
Same as ZM-
**
(normally 19200bps)
3
1
ON
OFF
The recommended communication parameter setting of both PC and ZM-
**
is as follows:
2 FUJI PC • 1
Comentarios a estos manuales