Sharp JX-9400 Información técnica Pagina 26

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 211
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 25
Applying again the integral mean value theorem, we get:
m ¼ Q
s;i
ð
0
Þ
ð
t
f
0
CðtÞdt with 0 <
0
< t
f
ð1:20Þ
Combining Equations 1.18 and 1.20, we get:
Q
i
ðÞ¼Q
s
ð
0
Þ
m
M
ð1:21Þ
There are sampling pumps with controlled constant flow rate. These easily
enable Q
s;i
to be kept constant, and in most cases it is possible to keep the
airflow rate constant in supply and exhaust during the experiment.
Simple and cheap air change rate measurement using CO
2
concentration decays
Method
CO
2
generated by occupants can be used as a tracer gas, since it is easy and
cheap to measure. There are compact and light CO
2
analysers on the market
that include a data logger. Peak value of the CO
2
concentration during
occupancy is an indicator of the minimum airflow rate per person. Analysis
of the decays observed when the occupants leave the building provides the
nominal time constant of the ventilated space, which is directly dependent on
the outdoor airflow rate from the ventilation system and infiltration.
Depending on the state of the ventilation system during the decay, this
method provides either the total outdoor airflow rate provided by the system,
or the infiltration rate. When combined with a simple pressure differential
measurement, this method can also be used to check airtightness of building
envelopes.
Equivalent outdoor airflow rate
Air may enter into a measured zone not only directly from outdo ors, but also
from neighbouring zones, whose CO
2
concentration may differ from outdoor
air. These inter-zone airflows influence the CO
2
concentration in the measured
zone, but can be measured only with complex and expensive techniques (see
Chapter 1, ‘Application to buildings, multi-zone’). The concept of equivalent
outdoor airflow rate is introduced to offset this inconvenience. It corresponds
to the outdoor airflow rate that would result in the same CO
2
concentration
in the measured room without inter-zone airflows. In the following, this quan-
tity is referred to as ‘outdoor airflow rate’.
Equivalent outdoor airflow rate per person
An adult person produces on average and for most of the time (i.e. when quiet
or doing light work with about a 100 W metabolic rate) about 20 litres per hour
(l/h) of CO
2
. At steady state, and assuming that occupants are the only CO
2
sources, the equivalent outdoor airflow rate per person, Q
e
, is related to CO
2
Airflow Rates in Buildings 5
Vista de pagina 25
1 2 ... 21 22 23 24 25 26 27 28 29 30 31 ... 210 211

Comentarios a estos manuales

Sin comentarios