Table 6.11 IAQ strategies for ducts
Design Operation
Prevent ducts from becoming a source of pollution
Use duct processed withou t oil, and which
does not emit pollutan ts itself (label or
smell)
Interior surfaces should be smooth, avoid
sharp edges or self-tapping screws in
ducts
Inspect ducts at least once a year and
clean if necessary
Prevent dust accumulating during operation or debris from construction
Keep duct ends closed until in operation
Keep accessories packed in closed boxes
Remove packaging just before installation
Prior to first operation, check all parts in
contact with the airflow for cleanliness,
and reclean if necessary
Install a filter system upwind of the ducts
Inspect ducts at least once a year and
clean if necessary
Check filter system that provides clean air
to duct at least once a year
Prevent condensation points
Add insulation material outside the ducts
Prevent condensation from humidifiers
Other recommendations
Limit flexible air ducts (difficult to clean)
Avoid sealant with high emission and do
not attach tapes or tags
Install service openings
Install stiffeners and other fittings in such a
way that deposits of dirt are prevented
and cleaning can be carried out
Check location and service openings,
especially in spaces with suspended
ceilings Very often service openings in
ducts are useless because there is no
opening in the suspende d ceiling or there
are cables under the service opening
Contaminants in Air Handling Units 129