Piston-type ventilation
See displacement flow.
Pitot tube
Anemometer measuring the difference between the pressure in a tube facing
the flow, in which the flow is stopped, and the pressure along a side of the
tube.
Pollutant removal effectiveness
See ventilation efficiency.
Pollution migration
Descriptive term for the movement of indoor air pollutants throughout a
building.
Pollution source
Any object, usually within a building, that produces a substance that will
contaminate the internal environment.
Power law
Flow equation in whi ch the airflow rate through the building envelope is propor-
tional to a power of the pressure differential.
Ppm
Unit for expressing volume concentration, which is a part per million (10
6
)or
a cubic centimetre per cubic metre.
Pressurization
Airtightness measuring technique using a fan to pressurize the measured
volume at a constant pressure. See also fan pressurization.
Pressure differential
Usual term for the differen ce in pressure across a building envelope or compo-
nent, whether caused by natural or artificial means.
Pressure tap
Point at which pressure is measured.
Pulse injection technique
Tracer gas measuring technique in which the tracer is injected in a short pulse.
Purging flow rate
Part of the airflow rate, which effectively removes the contaminants out of
the location of interest. It is the product of the airflow rate and the ventilation
efficiency.
Purpose-provided openings
Openings in the building envelope for the specific purpose of supplying or
extracting ventilation air.
Quadratic law
Flow equation in which the pressure differential is related to the airflow rate by a
quadratic polynomial.
182 Ventilation and Airflow in Buildings