Chapter 5 Operating Instructions
C4000 Standard/Advanced
42 © SICK AG • Industrial Safety Systems • Germany • All rights reserved 8009861/WA65/2012-06-12
Subject to change without notice
Installation and mounting
How to calculate the minimum distance D
s
according to ANSI B11.19:2003@04,
A
nnex D and Code of Federal Regulations, Volume 29, Part 1910.217 … (h) (9) (v):
T
he following calculation shows an example calculation of the minimum distance.
Depending on the application and the ambient conditions, a different calculation may be
necessary.
Calculate D
s
using the following formula:
D
s
=H
s
× (T
s
+ T
c
+ T
r
+ T
b
m
) + D
p
f
Where …
D
s
= The minimum distance in inches (or millimetres) from the hazardous point to the
detection point, plan or zone
H
s
= A parameter in inches/second or millimetres/second, derived from data on
approach speeds of the body or parts of the body. Often 63 inches/second
(1600 millimetres/second) is used for H
s
.
T
s
= Stopping time of the machine tool measured at the final control element
T
c
= Response time of the control system
T
r
= Response time of the presence-sensing device and its interface
T
bm
= Additional response time allowed for brake monitor to compensate for wear
Any additional time delays must be accounted for in this calculation.
D
pf
= An additional distance added to the overall minimum distance required. This
value is based on intrusion toward the hazardous point prior to actuation of the
electro-sensitive protective equipment (ESPE). Values range from 0.25 inches to
48 inches (6 to 1220 millimetres) or more depending on application.
Example:
In opto-electronic protection, such as with a perpendicular safety light curtain
applications with object sensitivity (effective resolution) less than 2.5 inches (64
millimetres), the D
pf
can be approximated based on the following formula:
D
pf
(inches) = 3.4 × (object sensitivity – 0.276), but not less than 0.
Note
Note
Vista de pagina 41
1 2 ... 37 38 39 40 41 42 43 44 45 46 47 ... 123 124

Comentarios a estos manuales

Sin comentarios

Magnum Energy AC Load Diversion Controller (ACLD-40) manuali

Manuali dei proprietari e guide per l'utente per Sensori Magnum Energy AC Load Diversion Controller (ACLD-40).
We fornisce 1 manuali pdf Magnum Energy AC Load Diversion Controller (ACLD-40) per scaricare gratuitamente in base al tipo di documento: Manuale Utente






Più prodotti e manuali per Sensori Magnum Energy

Modelli Tipo di Documento
AC Transfer Switch (CSW-TS15) Manuale Utente   Magnum Energy AC Transfer Switch (CSW-TS15) User Manual, 4 pagine
CSW1012 Manuale Utente   Magnum Energy CSW1012 User Manual, 24 pagine
CSW Remote Switch (CSW-RS) Manuale Utente   Magnum Energy CSW Remote Switch (CSW-RS) User Manual, 4 pagine
MM612 Inverter Manuale Utente   Magnum Energy MM612 Inverter User Manual, 44 pagine
AGS Network (ME-AGS-N) Manuale Utente   Magnum Energy AGS Network (ME-AGS-N) User Manual, 103 pagine
AGS Stand Alone (ME-AGS-S) Manuale Utente   Magnum Energy AGS Stand Alone (ME-AGS-S) User Manual, 32 pagine
Smart Battery Combiner (ME-SBC) Manuale Utente   Magnum Energy Smart Battery Combiner (ME-SBC) User Manual, 20 pagine
ME-125F Manuale Utente   Magnum Energy ME-125F User Manual, 2 pagine
Battery Monitor Kit ME-BMK Manuale Utente   Magnum Energy Battery Monitor Kit ME-BMK User Manual, 39 pagine
ME-300F Manuale Utente   Magnum Energy ME-300F User Manual, 2 pagine
ME-MW-E Manuale Utente   Magnum Energy ME-MW-E User Manual, 19 pagine
ME-MW-W Manuale Utente   Magnum Energy ME-MW-W User Manual, 20 pagine