182 • I/O Modules
Configuration and Parameterization of the I/O Modules
WAGO-I/O-SYSTEM 750
Bus System
PFC
6
0
1
Module is mapped into the field bus PA and PFC-PA
Module is exclusively mapped into the PFC-PA
Plug
5
0
1
Module is physically not present
Module is physically present (default)
PA-Diag
4
0
1
Diagnostics is mapped into the Input-PAB
locked
released
DiagEn0
2
0
1
Diagnostics idle run, short circuit on channel 1
locked
released
DiagEn1
3
0
1
Diagnostics idle run, short circuit on channel 2
locked
released
Italic cannot be changed