Sharp R-342D Manual de instrucciones Pagina 336

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 353
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 335
5-122 23. MODICON PLC
23. MODICON PLC
Available PLCs
Communication Setting
The recommended communication parameter settings of the PLC and the ZM-300 series is as follows:
Available Memory
The available memory setting range varies depending on the PLC model. Be sure to set within the
range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro
programs.
Select PLC Type PLC Unit/Port Connection
Modbus RTU Modbus RTU Modbus RS-232C [Wiring Diagram 1]
Item Setting on PLC ZM-300 Comm. Parameter Setting
Baud rate 9600 bps 9600 bps
Port 1 1
Parity Even Even
Transmission code
Data length 8 8
Stop bit 1 1
Memory TYPE Remarks
4 (holding register) 0
3 (input register) 1
0 (output coil) 4
1 (input relay) 6 Read only
Vista de pagina 335
1 2 ... 331 332 333 334 335 336 337 338 339 340 341 ... 352 353

Comentarios a estos manuales

Sin comentarios